All Products :

INDOOR DISCONNECTORS
TYPE : TND
Indoor, 3-Pole Isolating Switch
TS 565, DIN 43607

Voltage Class 12, 24 and 36 kV
Rated Currents 400, 630, 1250 and 1600 Amp.

 

Indoor Disconnectors
Indoor-Earthing Switch
Single - or 3-Pole Fuse Base

Printer Friendly
PDF Brochure

The indoor isolating switches given in this list are for switching with no-current. They are produced under the technical knowledge of FRITZ DRIESCHER / Moosburg (Germany), and have positively proven themselves in many installations with their superior quality. They have a robust basic frame of welded profiled steel. Double isolating knives are made of copper, nickel or silver plated. The contact is effected by cutoff and turning'point by means of distingue line contact. Rich sized cross sections and appropriate contact pressure guarantee a safe and easy operation for a long period of years.

RATED VOLTAGE Ur kV
12
24
36
RATED CURRENT Ir A
630
1250
1600
630
1250
1600
630
1250
1600
RATED PEAK WITHSTAND CURRENT Ip kA
50
75
100
50
75
50
30
75
80
RATED SHORTTIME CURRENT Ik kA
20
30
40
20
30
20
16
30
30
Rated impulse withstand voltage 1,2/50 c/s CONDUCTOR to
EARTH
kV
75
125
170
CONDUCTOR to CONDUCTOR kV
75
125
170
EARTH kV
85
145
195
Rated withstand voltage at 50 c/s CONDUCTOR to
EARTH
kV
28
50
70
CONDUCTOR to CONDUCTOR kV
28
50
70
EARTH kV
32
60
80


class Ir a b c d e f ~g ~h ~H p w x y Weight Kg.
12
400
280
310
600
640
250
360
454
275
250
210
115
425
425
23,5
630
370
17,5
24
400
350
380
710
750
300
410
594
325
300
275
155
550
550
33,5
630
420
629
360
335
36
400
450
500
1000
1040
400
510
833
375
345
400
195
800
800
58,0
630
520

[Back]

For more information contact us.

3-POLE
INDOOR-EARTHING SWITCH

Spring quick action Type: TDYC
Normal hand-action Type: TDY

Class
kV
Rated Shorttime Current Ik
(1 sec.) kA
Rated Peak withstand current Ip
kA
C d H L P X y
12 25 63 600 640 300 322 210 425 425
31,5 80 370
17,5 16 40 710 750 300 400 275 550 550
31,5 320
24 16 63* 325 425
31,5 345
36 12,5 31,5 1000 1040 445 535 400 800 800
25 63** 475 590
* The making capacity is limited by 40 kA.
**The making capacity is limited by 31.5 kA
The earthing switch can be quick-action if desired. Making and breaking is realized by a spring action.

SINGLE - or - 3-POLE
FUSE BASE


They are designed for use mV-Fuses in compliance with the standards DIN 43625,
TS 1259- IEC 60282-I

Rated current of the contact system is 200 Amp.
Without Breaking Mechanism
Type ADO : Suitable for HV-Fuses with optical indicator
With Breaking Mechanism
Type ADM/.. : Suitable for HV-Fuses with Striker Pin. It gives the advantages of getting an impulse for an alarm system / or for a shunt release, by means of a switch (4-12 poles)

Class KV
In
a
b
c
d
e
f
~H
~h
P
X
y
Weight Appr. Kg.
ADO
ADM
12
200
280
480
600
640
325
445
235
320
210
320
320
15,5
17,9
17,5
24
200
350
650
710
750
475
505
300
385
275
380
380
26
29
335
420
36
200
450
760
1000
1040
570
690
425
510
400
520
520
40,0
43,7

[Back]

 
 
Copyright © 2005 Ưnter - Teknik
 