Fuses are not suitable devices for protection against overload. They work safely only over the Imin value. Namely it does not operate safely within the range of In (rated current value) and Imin value, and in some cases the fuses may be damaged. Depending on the quality of the melting line used and the construction of the fuse, Imin shows changes.
Naturally the expansion of the safe operating area for a fuse is a great advantage. For this reason Imin should be as small as possible.
If loading between In rated current and
Imin is a must and cannot be prevented, then it is recommended
to use load break switches with thermal protective fuses.
In that case, before the extreme heat produced in the
fuse reaches the tolerance level of the electro porcelain
tube of the fuse, the thermic system works to loosen the
striker pin which in turn switches off the loadbreak switch
in three phases, thus minimizing the risk area.
CONSTRUCTION
The principle component of the fuse link insert is a starshaped rod. The pure silver wire or band is wound around the starshaped rod, thus forming completely similar small cells all along the body. The lengths and cross section of the silver in each cell is completely the same. Many partial arcs form all along the melting line and the thermal heat is evenly distributed in the fuse body thus attaining a higher breaking capacity. The tubes are definitely durable to extreme heat, non inflammable and insulated. More over, especially the outdoor type fuses are durable to atmospheric changes, corrosion, salts, acids and alkali gases. They do not absorb water or moisture. In case the fuse is blown, the body provides insulation. Therefore it must provide the needed insulation level rain or shine. To attain these properties, the ideal material to be used is ELECTRO PORCELAIN.
To be durable enough to resist the high pressure and heat that will form, the porcelain tubes should be,
at the least, conforming with the C120 – C130 IEC 672 standards. Metal caps on both ends are made of
electrolytic copper of 1 - 1.2 mm. thickness and are nickel or silver plated ( 4-6 microns) against oxidation.
The caps are tightly pressed onto the porcelain tubes using silicone seal. Metal pieces in the inner body
are manufactured from electrolytic copper. Depending on the In value, they are either silver coated or
copper striped of oil. To obtain perfect current conductivity and fuse characteristics the silver wires and
bands are welded onto the metal body by point-welding source. The inner body and outer body are also
attached by point welding source.
The mechanic strength and water insulation of our fuses are attained by mounting the metal and optical glass caps on both sides , sealing with high heat resistent silicone and special pressing methods.

TYPES
The sizes of all types conform to TS EN 60282-1 - DIN 43625 and are suitable for indoor
and outdoor use.
|
FUSE WITH OPTICAL INDICATOR |
OPTİCAL INDICATOR (TYPE:
........ /OPT)
The fuses with optical indicators types H220 and H221 have a mechanism showing that the fuse is blown. When the fuse is blown, a small red cap falls into the transparent capsule at the end of the tube.
STRIKER PIN (TYPE: ........ /ACT)
TS EN 60282-1, Table XII - (Medium)
When a fuse is blown a pin is strongly pushed out. Hence,
you can see blown fuse and also automatically iniate another system (e.g.: a switch, notification
of an alarm system).
STRIKER PIN FORCE
There are three options:
A) 100-120 N
B) 80N
C) 50N
The preference should be stated while ordering. If it's
necessary to open a switch mechanically, then the A or
B choices are advisable.

THERMAL
PROTECTION (Current limiting type, back - up class)
The operation of medium voltage fuses with thermal protection is determined by minimum breaking current (Imin). These fuses only work safely over the I min value. Namely, between the values In (rated current) and I min
a safe operation cannot be guaranteed.
The over loading of fuses in between these values may cause explosion and big damage.
The melting element of the fuse will melt in just one or a few small pieces and the arc produced here will continue to travel within the circuit, leading to extreme thermal forces.
In order to eliminate this problem, our fuses type H220 ACT and type H221 ACT, have a thermal protection system. In this special design, the fuses have a striker device inside the fuse link which is released before the temperature reaches a value endangering the thermal strength of the porcelain tube, and initiates opening of all poles by the help of a switch - disconnector.
Fuses with the thermal protection system should be used in combination with a switch. When used in combination with automatic breaking switch or especially with SF6 gas insulated "Ring main unit" pannels, fuses with thermal protection system should be prefered..
Please do not hesitate to contact us for more information
on thermal protection.
SHORT
CIRCUIT CURRENT LIMITATIONS
Our medium-voltage high-breaking-capacity fuse links open the circuit during the current rise in the first loop of short-circuit current.They are thus current-limiting.
The figure below shows the progress of a short-circuit operation. Without a fuse in the circuit, the short-circuit
current would rise as the prospective current Ik shown as a broken line.
However, the current-limiting action of the fuse-link permits the melting current IS to rise only to the cut-off value ID(full line). The current decreases during the arcing time tL with increasing arc length and is finally broken in the area of a voltage zero passage.
The current-limiting action of the fuse-links relieves the apparatus and parts of the system of thermal and dynamic stresses. It is clear that the application of current-limiting fuse-links is particulary advantageous in older installations which have not been designed for the increasing short-circuit levels of the system.
The value of the cut-off current is influenced by the design of the fuse-link. It further depends on the rated current and the instant on the voltage wave at which the short-circuit occurs.
lS Melting current
ID Cut-off current
Ik(t) Prospective short-circuit current (fuse replaced by metallic link)
IP Impulse short-circuit current
tS Pre-arcing time
tL Arcing time
The cut-off current of our m.v.
h.b.c. fuse links, which can be taken
from the diagram, are a function of the
prospective short-circuit current (r.m.s
value of the symmetrical component)
and of the rated current.
The prospective short-circuit
current is expressed by the r.m.s. value
of the symmetrical component of the
current which would flow at the location
of installation if the fuse were replaced
by a solid link.
The cut-off currents determined
from the diagram are the maximum
values which might occur for a given
r .m.s. value of the symmetrical
component of the prospective shortcircuit
current with any degree of
asymmetry and the highest rate of
current rise. Actual values are thus, as
a rule, less than the values determined
here.
RATED
BREAKING CURRENT CAPACITY
The rated breaking current capacity depends on the inner structure of the fuse. The special construction of the fuse link insert ensures that short pre-arcing and arcing times are obtained on operation and that multiple partial arcs are formed. Accordingly the amount of heat generated in the fuse link is relatively small and uniformly divided over the whole length of the fuse elements. These factors provide the increase in the rated current breaking capacity of a fuse.(To check the rated breaking current values of
İNTER- TEKNİK fuses please use the link)
DANGEROUS
EXTREME VOLTAGES
When the short circuit current is broken, the voltage will jump. Not to let any damage happen to devices in the installation due to this voltage jump, peak value is limited as 2.Un. 2 in the TS and VDE norms. The advantage of using these fuses to protect your transformers, cable outlets and voltage
transformers is obvious.
MINIMUM
OPERATING VOLTAGE
- In case higher breaking capacity is needed
or
-
when an installation with low operating voltage is going to be renewed to a higher operating voltage unit
(e.g.: because the voltage will be 30 kV, the old installation with an operating voltage of 10 kV will be
renewed as 30 kV series) a higher Un valued fuse might be used. If the operating voltage is small in regard
to the Un value of the fuse, the voltage jump while the circuit breaks may be extremely high (depending
on the construction of the fuse). In INTER-TEKNIK fuses the ratio allowable is 1/2, meaning that in an
operating voltage of 10 kV, a fuse with Un = 20 kV can be safely used.
For this reason, keeping in mind that the breaking capacity should be suitable to the operating voltage,
while giving your orders you should also state the D dimension of the fuse you have selected.
Example: In an installation where operational voltage is 10 kV, a fuse of D=442mm can be used (equivalent
to a fuse Un=24 kV).
POWER
DISSIPATION
The heat produced in the fuse should
be released to the atmosphere. In indoor areas and
insulated panels, heat is a vital factor effecting the
nominal values of the devices.
Approximate power dissipation of the fuse may be calculated
as (R x I2 x K); the fuses inner resistance (R value at temperature 20°C) increases due to heating. K factor indicating this increase about
1,4 - 2 at the In value. For current values lower then
In, this factor takes a value of 1,1 - 1,4.
TIME
CURRENT CHARACTERISTICS OF THE MEDIUM VOLTAGE HIGH BREAKING
CAPACITY FUSES

SELECTIONS
RATED VOLTAGE
Must be properly selected in accordance with the operational voltage.
RATED BREAKING
CURRENT
Proper fuse selection according to the short circuit load of the network is important. In some special occasions, if necessary, a fuse of a higher voltage group may be selected or two fuses may be connected in serial, thus obtaining a higher rated breaking current capacity.
RATED CURRENT
This value denotes the naming of the fuse. Essentially the selection of the fuse according to the purpose
and the place of use is very important. Heat is one of the most important factors.
For example in the protection of a transformer, if a fuse of In = 6 A is suitable outdoors, when the same
transformer is used in a completely closed indoor area, then a fuse In = 10 A may be necessary.
In extreme cases where higher current values are necessary, two fuses with the same value connected
paralel can be used. But as the two fuses standing side by side will give heat to each other, a specific
tolerance level should be set.
DERATING FACTOR
The rated current is the current which a fuse link can carry continuously without altering the time/current characteristic
curve. At higher ambient temperatures as well as higher power losses generated by fuses of very high rated currents,
it is necessary to pay special attention to derating factors.
Depending on usage conditions and due to the overheating of the fuse body, it is advisable to reevaluate the choice
of fuse rating and use a fuse with a greater In value.
In fuses that operate with melting fuse elements, the heat of the fuse body is the main factor that effects the
functioning of the fuse. As it functions, the heat produced in the fuse should be transferred to the atmosphere in
an effective way. If the body of a fuse which is used in a closed environment gets excessively hot, then a fuse of
higher value should be used. For example, under normal conditions a fuse In=40 A might be suitable for the
protection of a transformer, but if because of environmental factors the fuse heats excessively, then a fuse of
In= 50 or 63 A should be used.
As the plants of our day are huge and growing in size, they require fuses with very high In values for their protection.
Meanwhile, as the In value of fuses increase, due to the physical limitations of material and production methods,
it becomes very difficult to keep the heat of the fuse at normal temperatures. Therefore, especially under these
circumstances special attention should be given to the DERATING FACTOR.
Due to their high starting currents, in the protection of electrical appliances such as motors, transformers or
capacitators, fuses with high In values should be selected. In other words, under normal operating conditions the
current passing through the fuse will be approximately half, under 25% overload it will be about 75% of the In value
of the fuse. Generally the nominal current of the fuse should be 2 or 3 times larger then that of the normal circuit
current. It is important to keep this fact in mind.
This means the fuses will warm less. As you evaluate, special attention should be given to this issue. For this reason,
on the labels of these fuses both current values are indicated.
For example “250 RC 160” means:
- the nominal current of the fuse In=250 A. (the starting current is taken into consideration)
- the current value of the continuous current passing through the circuit RC (rated current) is 160 A.
MOTOR PROTECTION IEC 60644

The first and important criteria in fuse selection is the value and the duration of the INRUSH current of the motor. The fuse should stand this inrush current. In selecting the fuse from the time-current curves, the tolerance on current rates given in the standards should not be neglected (± 20% on current value). The second criteria is the frequency of starting the motor which can lead to the aging of the fuse, which in turn might result in changes in the characteristics of the fuse. Depending on the frequency of the period of starting, the In value of the fuse may be uprated. In selecting your fuse, please keep in mind the following: Usually fuse +switch combinations are used for motor protection. If one of the fuses blow due to a fault, the striker pin initiates the switch to break the current in three phases.
-The breaking capacity of the fuse should be
greater than the short circuit load of the
establishment.
-The In value of the fuse should be greater than
the nominal power and overload value of the
motor. Derating should be done according to the
medium in which the fuse will be used, meaning
the In value of the fuse should be increased
accordingly.
-The In value should be decided upon with an
acceptable margin so that the fuse does not blow
during starting current period.
-Depending on the number of starting/shutting
of the motor, there will be material fatigue. In
value should be increased accordingly.
-The minimum breaking current (Imin) value of
the fuse should be smaller than the value of point
H (see diagram8).
For the coordination between the fuse and the
protection relay of the switch, and for all the
above listed issues please use the diagrams.



FUSE PROTECTION OF TRANSFORMERS IEC 60787
All tests and practices show that, when chosen correctly, current limiting m.v.fuses effectively protect transformers by breaking fault currents.
Various criteria have to be observed in selecting m.v.h.b.c. fuse-links for the short circuit protection of transformers.
Here are some of them:
- The rated current of the m.v.h.b.c. fuse-link must not be less than a certain value so as to protect operation of
the fuse-link from the transformer inrush current on switching on.
- The rated current of the fuse-link must be low enough so that the value of the current which might happen
during a short-circuit on the low voltage side of the transformer will not be less than the Imin value of the fuse. This means that the fuse will perform its breaking safely.
- The rated current of the medium-voltage fuse link must be sufficiently high to premit the overloading of the
transformer and assure selectivity between the fuses on the low voltage side.
- The rated current of the m.v.h.b.c. fuse-link must be as low as possible so that the fuse can break the current
quickly when a fault occurs in the transformer coils and assure the selectivity between the fuse and relay at the start of the mv supply feeder.
Taking the above mentioned points into account, selecting the m.v.h.b.c. fuse links in accordance with the tables below is recommended.
M.V.
and L.V. FUSE SELECTING TABLES FOR THE PROTECTION OF DISTRIBUTION
TRANSFORMERS

FUSE
PROTECTION OF CONDENSERS
The existence of numerous types of electrical
facilities and unknown circuit parameters usually complicates
fuse selection. When selecting, keep in mind the following criteria:
- The In value of the fuse should be high enough to withstand the continuous maximum load current and the allowable harmonic content.
- The In value of the fuse should be able to tolerate
the passing inrush value of the condenser bank.
- Voltage increases caused by temporary situations should
not be neglected and for security
purposes, a higher current class fuse should be selected.
- As for practical information, the In value of the fuse
should not be lower then 1,6-2 times that of the condenser's
full load current value.
WIRE
AND LINE PROTECTION
It should not be forgotten that wires and
lines will be exposed to overloading from time to time.
This situation may cause overloads between
the In value and I min value of the fuse, eventually causing
extreme heating and damage. For this reason the fuse should
be selected according to the maximum load that the cable
or line can carry.
OTHER
POINTS
- It is not correct to use a fuse that has
been dropped or exposed to any sort of impact without
testing it.
- In a three - phase installation, unless you are definetly
sure that only the blown fuse was exposed to a faulty
current, all three must be replaced, because the fuses
that are not blown also might have reached a point very
close to functioning and their characteristics might have
changed.
- As a precaution the blown fuse, should be changed 5
- 10 minutes after it has blown.
VOLTAGE
TRANSFORMER PROTECTION
Because of the low capacity of voltage transformers, m.v. fuses cannot protect the voltage
transformer from their own default currents effectively. More often, they are used to seperate the defected voltage transformer from the
system. The principle in choosing the fuse is to use a
fuse big enough to endure the inrush voltage of the
transformer. This means that the fuse should be at the
most In=1- 2 A. The very thin melting line used in the
fuses with small In values may lead to a "corona"
effect. Therefore, the fuse should definitely be used
as far away from earthed metal parts as possible.
THINGS
TO INDICATE WHILE ORDERING
| Type |
: |
H220 - H221 |
| Indicator |
: |
OPT (Optical) or ACT (striker pin) |
| If ACT, the force of the
striker pin |
: |
F=50N ; F=80N ; F= 120N |
| Thermal protection |
: |
TRM |
| Rated voltage (Un) kV |
: |
from the table |
| Length (D) mm |
: |
from the table |
| Rated current (In) A |
: |
from the table |
| Example 1 |
Example 2 |
H220/ACT
Un = 36 kv
In = 40 A |
F=80N
D = 537 mm
I1 = 31,5kA |
H221/OPT
Un = 12 kv
In = 160 A |
D = 442 mm
I1 = 31,5 kA |
POTENTIAL TRANSFORMER PROTECTION FUSE

Rated voltage
Un (kV) |
Rated current
In (Amp) |
L
mm |
D
mm |
Breaking capacity
I1 (kA.) |
Approx. (Weight)
kg. |
| 5,5 |
1 |
127 |
20 |
16 |
0,090 |
| 2 |
| 7,2 / 8,25 |
1 |
190 |
20 |
16 |
0,130 |
| 2 |
| 7,2/12/15,5 |
1 |
254 |
20 |
16 |
0,175 |
| 2 |
| 15,5/25,5 |
1 |
340 |
20 |
16 |
0,230 |
| 2 |
| *36 |
1 |
400 |
36,5 |
16 |
0,935 |
| 2 |
* Optional: if demanded, the fuse can be produced with indicator.
Note: please indicate Un, In and L values while you are giving orders.
M.V. H.R.C. FUSE DIMENSIONS

(*) Pease keep in mind the derating factor.
Please check the catalogue for more information.
 |
| Type : .........../ OPT |
Type : .........../ ACT |
Un KV |
TYPE |
In
Amp. |
I3
Amp. |
I1
kA |
D
mm |
S
mm |
L
mm |
C2
Cap Diameter
mm |
C1
Tube Diameter mm |
Weight
Kg |
| 36 KV |
H220 |
1 |
6 |
31,5 |
537 |
570 |
603 |
55 |
53 |
2,8 |
| 2 |
12 |
31,5 |
| 4 |
4xln |
31,5 |
| 6,3 |
" |
31,5 |
| 10 |
" |
31,5 |
| 16 |
" |
31,5 |
| 20 |
" |
31,5 |
| 25 |
" |
31,5 |
| 31,5 |
" |
31,5 |
| 40 |
" |
31,5 |
61 |
58 |
3,5 |
| 50 |
" |
25 |
| H221 |
63 |
" |
25 |
78 |
74 |
5,5 |
| 80 |
" |
25 |
86 |
84 |
7 |
| 100 |
" |
25 |
| *125 |
" |
25 |
| *160 |
" |
20 |
| *200 |
" |
20 |
| *250 |
" |
16 |
| *315 |
" |
16 |
| 24 KV |
H220 |
1 |
6 |
31,5 |
442 |
475 |
508 |
55 |
53 |
2,3 |
| 2 |
12 |
31,5 |
| 4 |
4xln |
31,5 |
| 6,3 |
" |
31,5 |
| 10 |
" |
31,5 |
| 16 |
" |
31,5 |
| 20 |
" |
31,5 |
| 25 |
" |
31,5 |
| 31,5 |
" |
31,5 |
| 40 |
" |
31,5 |
| 50 |
" |
25 |
61 |
58 |
2,9 |
| H221 |
63 |
" |
25 |
78 |
74 |
4,6 |
| 80 |
" |
25 |
| 100 |
" |
25 |
| *125 |
" |
25 |
86 |
84 |
6 |
| *160 |
" |
25 |
| *200 |
" |
25 |
| *250 |
" |
20 |
| *315 |
" |
20 |
| 17,5 KV |
H220 |
1 |
6 |
31,5 |
367 |
400 |
433 |
55 |
53 |
1,9 |
| 2 |
12 |
31,5 |
| 4 |
4xln |
31,5 |
| 6,3 |
" |
31,5 |
| 10 |
" |
31,5 |
| 16 |
" |
31,5 |
| 20 |
" |
31,5 |
| 25 |
" |
31,5 |
| 31,5 |
" |
31,5 |
| 40 |
" |
31,5 |
| 50 |
" |
25 |
61 |
58 |
2,45 |
| 63 |
" |
25 |
78 |
74 |
4 |
| H221 |
80 |
" |
25 |
| 100 |
" |
25 |
| *125 |
" |
25 |
86 |
84 |
5 |
| *160 |
" |
25 |
| *200 |
" |
25 |
| *250 |
" |
20 |
| *315 |
" |
20 |
Un KV |
TYPE |
In
Amp. |
I3
Amp. |
I1
kA |
D
mm |
S
mm |
L
mm |
C2
Cap Diameter
mm |
|
|
| 12 KV |
H220 |
1 |
6 |
40 |
292 |
325 |
358 |
55 |
53 |
1,6 |
| 2 |
12 |
40 |
| 4 |
4xln |
40 |
| 6,3 |
" |
40 |
| 10 |
" |
40 |
| 16 |
" |
40 |
| 20 |
" |
40 |
| 25 |
" |
40 |
| 31,5 |
" |
40 |
| 40 |
" |
40 |
| 50 |
" |
40 |
| 63 |
" |
40 |
61 |
58 |
2,0 |
| H221 |
80 |
" |
40 |
78 |
74 |
3,25 |
| 100 |
" |
31,5 |
| *125 |
" |
31,5 |
86 |
84 |
4,2 |
| *160 |
" |
31,5 |
| *200 |
" |
31,5 |
| *250 |
" |
25 |
| *315 |
" |
25 |
| 7,2 KV |
H220 |
1 |
6 |
40 |
192 |
225 |
258 |
55 |
53 |
1,15 |
| 2 |
12 |
40 |
| 4 |
4x in |
40 |
| 6,3 |
" |
40 |
| 10 |
" |
40 |
| 16 |
" |
40 |
| 20 |
" |
40 |
| 25 |
" |
40 |
| 31,5 |
" |
40 |
| 40 |
" |
40 |
| 50 |
" |
40 |
| 63 |
" |
40 |
61 |
58 |
1,15 |
| H221 |
80 |
" |
40 |
78 |
74 |
3 |
| 100 |
" |
31,5 |
| *125 |
" |
31,5 |
86 |
84 |
3,9 |
| *160 |
" |
31,5 |
| *200 |
" |
31,5 |
| *250 |
" |
25 |
| *315 |
" |
25 |
| NOTE: |
1) Please don’t forget to take the derating factor (*) into consideration You can find more information on the subject inside the catalogue |
| 2) Please contact us if your demands for In values are higher than those in the above table. |